Protection Trip Time & Time-Current Curve Calculator

MCB · IDMT Relay · Fault Current · TCC Plot

Select a protective device, enter its settings and a prospective fault current, and immediately see the time-current characteristic curve with the fault current plotted against it. Supports LV circuit breakers (Type B/C/D magnetic trip bands per IEC 60898-1) and IDMT overcurrent relays (IEC 60255 inverse-time curves). Circuit breaker results are shown as an operating-time range where the standard itself defines a tolerance band, not a fabricated exact figure.

Compare Against a Second Breaker (Device B)
MAXIMUM OPERATING TIME
≤ 0.1 s
Trip Type: Magnetic
Fault current: 2 kA
Fault type: Three-Phase Fault
Rating: 32 A
Current multiple: 62.5× In
The magnetic (short-circuit) element governs at this current — it operates well before the slower thermal element. 0.1 s is the IEC 60898-1 guaranteed upper bound, not a measured point value.

Results for guidance only. Verify against current standards and manufacturer data.
Not a substitute for engineering judgement or a licensed professional.

100A1.0kA10ms100ms1.0s10s100s1000s10000sCurrentOperating TimeIn = 32 AINSTThree-Phase Fault: 2 kA
Indeterminate trip bandGuaranteed instantaneousFault operating point

Methodology

LV circuit breaker (MCB) — fault/magnetic region: for Type D, the instantaneous trip region is modelled per IEC 60898-1 cl. 9.10.2, which defines a two-point test — a hold threshold (guaranteed no instantaneous trip) and a trip threshold (guaranteed instantaneous trip within 0.1s):

Type D Hold Threshold
I<10×In    no instantaneous trip guaranteedI < 10\times I_n \;\Rightarrow\; \text{no instantaneous trip guaranteed}
Type D Trip Threshold
I20×In    instantaneous trip within 0.1 sI \geq 20\times I_n \;\Rightarrow\; \text{instantaneous trip within } 0.1\ \mathrm{s}

Between these two thresholds, the standard does not define a single trip time — the result is shown as a range, not a fabricated precise figure.

Assumptions & Limitations

  • MCB magnetic trip bands are the IEC 60898-1 standard ranges — individual manufacturer product families may specify a narrower band (e.g. some Type D families use 10–14× In rather than the full 10–20× In standard range). Verify against the specific device's datasheet for coordination-critical work.
  • Calculated times are a protection-analysis aid — actual device behaviour should be confirmed against manufacturer TCC data
  • Engineering judgement and a full coordination study remain required for final protection settings